 FXC7000 AC-DC Series Data Sheet
r Front-End Distributed Powe
Features
* Three-phase AC input * Suitable for 3U or 5U height mounting * Single-wire current share or Droop current share * Remote voltage adjust and current monitoring * Overtemperature, overload, and overvoltage protection * LED supply status indicators * Current-share control for up to 30 units
FXC7000 Front and Rear Views
* Front panel selectable-input-range
Description The FXC7000 Series of standalone or rack-mounted power systems provides true AC front-end capability to automatic test equipment, telecom, data communications, and other distributed power designs. The FXC systems may be paralleled up to 210 kW of output power and are intended for chassis-mounted installations with bolted connections. These power supplies provide excellent protection against input voltage transients. The FXC has its fan located at the front of the supply, and voltage adjust, indicator lights, output bussbars, and connectors on the rear. Airflow is from the front through Chassis-Mountable Model
MODEL OUTPUT VOLTAGE (NOTE 2) INPUT VOLTAGE RANGE 3-PHASE (VAC) ADJUSTMENT RANGE MAXIMUM OUTPUT CURRENT LINE REGULATION LOAD REGULATION (NOTE 1) INITIAL SETTING ACCURACY
the rear. Alarm, monitoring, and control signals are floating from the main output and can be referenced to the positive or negative output or sense line of the power supply. The output is floating with respect to the chassis and may be used as a positive or negative polarity supply. The FXC7000 Series meets international safety requirements and is CE Marked to the Low Voltage Directive. This series operates on three-phase European voltages as well as (up to) 480VAC, delta or wye.
FXC7000-48-S
48V
180 to 264 or 342 to 528
45.6V to 50.4V
145A
0.15%
0.2%
47.90V to 48.10V
NOTES: 1) With Remote Sense connected. 2). User-selectable input voltage ranges
Input Specifications
PARAMETER DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
Input Voltage - AC
Input Current Inrush Surge Current Input Frequency Hold-up Time Operating Frequency Power Factor
3-phase delta low input range, nominal. 3-phase delta high input range, nominal. Continuous deviation from the above nominals. Per phase at full rated load. FXC7000 at 180 VAC: Internally limited. Vin = 264VAC (one cycle). 25 C: Vin = 528VAC (one cycle). 25 C: AC input. After last AC line peak at full power. 208 VAC: 400 VAC: Switching frequency, fixed.
200 380 -10
50 17 13 100 0.90
240 480 +10 30 30 15 60
VAC % ARMS APK Hz ms kHz W/VA
AUG 18, 2006 revised to JAN 09, 2007
Page 1 of 4
www.power-one.com
FXC7000 AC-DC Series Data Sheet
Output Specifications
PARAMETER DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
Output Voltage Adjustment Range Output Power Output Current Efficiency Regulation
Ripple & Noise
Overshoot / Undershoot Minimum Loads Transient Response Turn-On Delay Turn-on Rise Time
An additional 1.0 Volt is provided to the output terminals to provide for load lead losses. Continuous duty rating. Continuous duty rating. Full rated load (208Vac). Load, Maximum deviation with 0 to 100% load change: With Remote Sense connected: With Remote Sense not connected: Utilizing Droop Current Share: Line, Under all specified operating conditions. Measured at mating connector w/ 0.01F + 10F Tant. 20 MHz BW: 100 MHz BW: Output voltage overshoot/undershoot at turn-on. Minimum loading required to maintain regulation. Maximum recovery time, to within 1% of initial set Time: point due to a 25% load change, 1A/S. Deviation: Time required for initial output voltage stabilization after power-up. Time required for output voltage to rise from 10% to 90%.
45.6
48
50.4 7000 145
V Watts A %
88
91 0.2 0.75 2.0 0.2 1 2 0
%
% p-p % A s % s ms
0 800 3.2 3 100
Interface Signals and Internal Protection
PARAMETER (NOTE 1,2) DESCRIPTION/CONDITIONS MIN NOM MAX UNITS
AC Power Fail Warning Auxiliary Power Current Monitor
Current Share Input Range Select Status Loss of Phase Warning Output Inhibit Output Interlock Output Overload Protection Output Overload Warning Output Short Circuit Protection Output Voltage Fault Signal Output Voltage Margin Overtemperature/ Fan Failure Warning Overvoltage Protection Power Supply Present Signal Remote Sense
Warning provided prior to Vout dropping 5% after loss of AC input. Output voltage - diode isolated. Inclusive of line, load, and initial tolerances. Output current. Monitor output current over a compliance range of 0~10V. Normal output: Total error current: Static sharing deviation as a percent of full-load rating Active: for loads >10%. Passive: Maximum signal resistance in high input voltage range selection. Warning provided prior to protective reduction in current limit. Voltage required to enable supply (0.5 mA sink). (NOTE 3) Voltage required to enable supply (6 mA sink). (NOTE 3) Straight line current limit (above approx. 5V Vout). Signal level on overload. Occurs on overload when Vout is below approx. 5V. Iavg: May operate in burst-mode. Deviation from adjusted Vout that is considered as a fault. Output voltage swing available through Margin pin (analog). Time between fault warning and shutdown. Latching shutdown. Latch style overvoltage protection. Resistance to logic ground upon insertion of supply. Maximum load lead loss compensation (round trip).
4 11.6
12.0
12.4 500
ms V mA mA/A mA %
0.10 0.5 0.5 5 10 0.10 1.0 1.0 156 90 4 5.0 5 5.2
500
149 2.2 25 3 4.8 100 55.2
ms V V A V A % % ms V V
57.6 1000
60.0 1.0
NOTES: 1) All logic outputs listed below feature a standard active pull-down output with 0.4V max at 40 mA sink capability, and a 100k pull-up to 5V. 2) In addition to those listed below, signals and front-panel LEDs are provided to indicate: overtemperature/fan fault, AC phase imbalance, output good, interlock open, and supply inhibited. The FXP also provides 4 LED's indicating output loading. 3) Both signals must be pulled to logic ground for the unit to operate. Enables are 100% redundant internally for applications where redundant inhibit is desirable. Contact factory for additional design details.
AUG 18, 2006 revised to JAN 09, 2007
Page 2 of 4
www.power-one.com
FXC7000 AC-DC Series Data Sheet
Safety, Regulatory, and EMI Specifications
PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS
Agency Approvals Electromagnetic Interference ESD Susceptibility Radiated Susceptibility EFT/Burst Input Transient Protection Voltage Sag Immunity Leakage Current
UL60950/CSA60950-00 (cULus), IEC60950 3rd Edition, EN60950 (TUV), CE marked for the Low Voltage Directive FCC CFR title 47 Part 15 Sub-Part B - Conducted. EN55022 / CISPR 22 Conducted. Per EN61000-4-2, level 4. Per EN61000-4-3, level 3. Per EN61000-4-4, level 4. Per EN61000-4-5 Line-to-Line: Line-to-Ground: Per SEMI F47-0200 FXC/FXP6000 Per UL60950 and FXC7000 at 240 VAC, 60 Hz: EN60950: FXC7000 at 400 VAC, 50 Hz: FXC7000 at 480 VAC, 60 Hz:
A A 8 10 4 4 3 Pending 5 7 10
Class kV V/M kV kV
mA
Environmental Specifications
PARAMETER CONDITIONS/DESCRIPTION MIN NOM MAX UNITS
Altitude Operating Temperature Storage Temperature Temperature Coefficient Relative Humidity Shock Vibration Airflow
Operating. Non-Operating. At 100% load: At 50% load: 0C to 70C (after 15-minute warm-up). Non-Condensing. Operating: half-sine 10 ms, 3 axis Non-operating: half-sine 10 ms, 3 axis Operating: swept sine 5-2000-5 Hz, 5-32 Hz, 0.02iDA, 32-2000 Hz Non-operating: random 10-2000 Hz Airflow provided through the supply from front to rear. 0 -40
10k 40k 40 70 85 .02 95 +20 +40 1 6.15 155 4.4 555 2.8
ASL Ft. C C %/C %RH GPK GPK Grms cfm m3/min lfm m/s lb kg
Weight
27 12
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective divisional president of Power-One, Inc. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.
AUG 18, 2006 revised to JAN 09, 2007
Page 3 of 4
www.power-one.com
FXC7000 AC-DC Series Data Sheet
FXC7000 OVERALL SIZE: 15.17" x 8.00" x 5.00" (385.3mm x 203.2mm x 127.0mm)
MAINTAIN 25 SQ IN MIN FREE AREA (FRONT AND REAR) FOR AIR COOLING
0.955" (24.3mm)
3.510" (89.2mm)
7.705" (195.7mm)
10.260" (260.6mm)
15.17" (385.3mm)
1.10" (27.9mm)
0.85" (21.6mm)
A
A
A
A
6.850" (174mm) 5.42" (137.7mm) 4.24" (107.6mm)
<--AIRFLOW
SIDE VIEW
A A A A
INSULATOR BLOCK
1.100" (27.9mm) 0.53" (13.4mm) A A A A
FOR MOUNTING, USE M4 X 0.7 SCREWS, 8PL (MARKED A) ON SIDE OR BOTTOM WITH MAXIMUM PENETRATION 3.8mm.
2 PL
3.60" 4.480" (91.5mm) (113.8mm)
0.480" (12.2mm)
2 PL 1.22" (31.1mm)
BOTTOM VIEW
A 0.955" A (24.3mm) A A
RECOMMENDED MOUNTING TORQUE 10.5 INCH LBS. (0.64N/M)
2 PL
DIA 0.25" (6.4mm)
0.70"2 PL (17.9mm) 1.10" 2 PL (28mm)
3.510" (89.2mm) 7.705" (195.7mm) 13.455" (341.8mm)
0.20" (5.1mm)
REAR VIEW
9 18 26 1 10 19
FRONT VIEW
5.00" (127mm)
AC INPUT PE L1 L2 DC OUTPUT L3
POS
M4 THREAD 13mm CENTER-TO-CENTER 10mm 26-PIN CONNECTOR AMP PN: 749030-1 PIN 1 8.00" (203.2mm)
INPUT VOLTAGE RANGE SELECT MODULE ROTATE 180 DEGREES FOR 240 VAC
0.06 (1.7) 2 PL
VOLTAGE ADJUST POT
NEG
5 LED INDICATORS
AC DC Vadj T
SIGNAL
MATING CONNECTOR: CONNECTOR SHELL... AMP PN 748365-1 CONTACTS... AMP PN 748333-2
480VAC
INPUT VOLTAGE DISPLAY CUTOUT
AUG 18, 2006 revised to JAN 09, 2007
Page 4 of 4
www.power-one.com


▲Up To Search▲   

 
Price & Availability of FXC7000

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X